EV & High-Draw · CEC Section 64 (Renewable Energy)
Solar System Load Calculator
Determine solar AC inverter output, solar backfeed breaker size, and verify against the CEC 120% busbar capacity rule for panel connection.
1. Solar Inverter & Main Panel Details
2. Solar Circuit & Busbar Compliance
CEC 120% Busbar RuleINVERTER MAX CONTINUOUS OUTPUT
31.7 Amps
REQUIRED SOLAR BACKFEED BREAKER
40 Amp 2-Pole
MAX ALLOWABLE BACKFEED BREAKER
40 Amps
Busbar Rule Compliant: Your 40A solar breaker fits within the 120% busbar limit without needing a supply-side tap.
CEC Section 64 Busbar & Interconnection Rules
- The 120% Busbar Rule allows total breakers (Main + Solar) to equal up to 120% of busbar rating: (Busbar Amps × 1.20) − Main Breaker Amps = Max Solar Breaker.
- Solar backfeed breakers must be positioned at the opposite end of the busbar from the main breaker to prevent busbar overheating.
- Solar PV installations in Ontario require microFIT / net-metering approvals from your local LDC (e.g., Elexicon, Hydro One) plus an ESA permit.